0%

Relay takpɔkpɔwo

AMR ƒe nyatakakaɖoɖoɖa

  • Current kple voltage inputs abe alesi wòhiã ene
  • Digital input kple output abe alesi wòhiã ene
  • Asikaka screen gã aɖe
  • RS232 kple RS485 melidzeƒewo
  • Kpekpeɖeŋu na IEC 61850 kadodo ƒe ɖoɖowɔɖi
AMR ƒe nyatakakaɖoɖoɖa
  • IEC 61850

    communication protocol

  • RS232 · RS485

    serial ports

  • Touch

    large touch screen

Ametakpɔnu ƒe dɔwɔwɔwo

U<ANSI 27

Takpɔkpɔ tso elektrikŋusẽ si mebɔ o (ANSI 27) .

Trips when the voltage falls below the setting.

U>ANSI 59

Takpɔkpɔ tso elektrikŋusẽ si gbɔ eme (ANSI 59) .

Trips when the voltage rises above the setting.

I>> / I>ANSI 50/51

Takpɔkpɔ tso elektrikŋusẽ si gbɔ eme si menye mɔfianu o (ANSI 50-51) .

Instantaneous (50) and IDMT time-delayed (51) tripping on overcurrent and short circuit.

IE>> / IE>ANSI 50N/51N

Anyigbadzikpɔnu si menye mɔfianu o (ANSI 50N-51N) .

Instantaneous and time-delayed protection against residual current and phase-to-earth faults.

I> →ANSI 67

Mɔfiame ƒe elektrikŋusẽ si gbɔ eme takpɔkpɔ (ANSI 67-67 TOC) .

Overcurrent that checks the power direction, operating only for forward or reverse faults.

IE> →ANSI 67N

Mɔfiame Anyigba Takpɔkpɔ (ANSI 67N-67N TOC) .

Directional earth fault, for ring networks and parallel feeders.

I2>ANSI 46

Negative component overcurrent takpɔkpɔ

Detects unbalance, broken conductors and single phasing from the negative-sequence current.

θ>ANSI 49

Agbatsɔtsɔ si gbɔ eme takpɔkpɔ (ANSI 49) .

A thermal model of the plant that trips before a cable, transformer or motor overheats.

CBFANSI 50BF

Safui ƒe kpododonu takpɔkpɔ (ANSI 50BF) .

Trips the upstream breakers when a breaker fails to open after a trip command.

I> ↑CLP

vuvɔ ƒe agba didi ƒe dɔwɔwɔ (CLP) .

Raises the settings for a while after a long-dead feeder is re-energised, avoiding nuisance trips.

I2f / I1fInrush

Inrush fifia deteksi dɔwɔwɔ

Recognises transformer inrush from the second harmonic and blocks false trips.

Id>ANSI 87

Vovototodedeameme takpɔkpɔ (ANSI 87) .

Compares the currents into and out of the plant and clears faults inside the zone fast.

Kɔmpiutadziɖoɖowo ƒe nɔnɔmewo

01Kɔmpiutadziɖoɖo sẽŋu aɖe le esi si zazã le bɔbɔe hena dɔ vovovowo ɖoɖo
02Ŋutete be woalé oscillograph siwo ade 200 ɖe mɔ̃ dzi, mɔzɔzɔ ŋuti nuŋlɔɖi
03Sedziwɔwɔ ƒe ƒuƒoƒo 4 le esi
04Signal Routing software module na dɔwɔwɔ ƒe dzesiwo dede asi na relay inputs kple outputs
05Ŋutete be woaɖe relay ƒe ɖoɖowo ɖe go le XRio ƒe nɔnɔme me

Relay ɖaseɖigbalẽwo

  • Ŋusẽ Ŋuti Numekuku Dɔwɔƒe