保護電驛

AMR繼電器

  • 根據需要輸入電流和電壓
  • 根據需要進行數位輸入和輸出
  • 大觸控螢幕
  • RS232 和 RS485 端口
  • 支援IEC 61850通訊協議
AMR繼電器
  • IEC 61850

    communication protocol

  • RS232 · RS485

    serial ports

  • Touch

    large touch screen

保護功能

U<ANSI 27

欠壓保護(

Trips when the voltage falls below the setting.

U>ANSI 59

過壓保護(

Trips when the voltage rises above the setting.

I>> / I>ANSI 50/51

無方向過電流保護

Instantaneous (50) and IDMT time-delayed (51) tripping on overcurrent and short circuit.

IE>> / IE>ANSI 50N/51N

無方向性接地保護(

Instantaneous and time-delayed protection against residual current and phase-to-earth faults.

I> →ANSI 67

定向過流保護(

Overcurrent that checks the power direction, operating only for forward or reverse faults.

IE> →ANSI 67N

定向接地保護

Directional earth fault, for ring networks and parallel feeders.

I2>ANSI 46

負極元件過流保護

Detects unbalance, broken conductors and single phasing from the negative-sequence current.

θ>ANSI 49

過載保護(

A thermal model of the plant that trips before a cable, transformer or motor overheats.

CBFANSI 50BF

按鍵失效保護

Trips the upstream breakers when a breaker fails to open after a trip command.

I> ↑CLP

冷負荷檢測功能(CLP)

Raises the settings for a while after a long-dead feeder is re-energised, avoiding nuisance trips.

I2f / I1fInrush

突波電流檢測功能

Recognises transformer inrush from the second harmonic and blocks false trips.

Id>ANSI 87

差動保護(

Compares the currents into and out of the plant and clears faults inside the zone fast.

軟體特點

01擁有強大且易於使用的軟體環境,用於設定各種功能
02能夠記錄多達 200 個示波器、行程日誌
03擁有4個監管組
04訊號路由軟體模組,用於將功能訊號分配給繼電器輸入和輸出
05能夠以 XRio 格式輸出繼電器設置

中繼證書

  • 電源研究所