0%

Rele proteksi

Relai AMR

  • Input arus dan tegangan sesuai kebutuhan
  • Input dan output digital sesuai kebutuhan
  • Layar sentuh besar
  • Port RS232 dan RS485
  • Dukungan untuk protokol komunikasi IEC 61850
Relai AMR
  • IEC 61850

    communication protocol

  • RS232 · RS485

    serial ports

  • Touch

    large touch screen

Fungsi pelindung

U<ANSI 27

Perlindungan tegangan rendah

Trips when the voltage falls below the setting.

U>ANSI 59

Perlindungan tegangan lebih

Trips when the voltage rises above the setting.

I>> / I>ANSI 50/51

Perlindungan arus lebih non-arah

Instantaneous (50) and IDMT time-delayed (51) tripping on overcurrent and short circuit.

IE>> / IE>ANSI 50N/51N

Perlindungan grounding non-arah

Instantaneous and time-delayed protection against residual current and phase-to-earth faults.

I> →ANSI 67

Perlindungan arus lebih terarah

Overcurrent that checks the power direction, operating only for forward or reverse faults.

IE> →ANSI 67N

Perlindungan Pembumian Terarah

Directional earth fault, for ring networks and parallel feeders.

I2>ANSI 46

Perlindungan arus lebih komponen negatif

Detects unbalance, broken conductors and single phasing from the negative-sequence current.

θ>ANSI 49

Perlindungan kelebihan beban

A thermal model of the plant that trips before a cable, transformer or motor overheats.

CBFANSI 50BF

Perlindungan kegagalan kunci

Trips the upstream breakers when a breaker fails to open after a trip command.

I> ↑CLP

fungsi deteksi beban dingin (CLP)

Raises the settings for a while after a long-dead feeder is re-energised, avoiding nuisance trips.

I2f / I1fInrush

Fungsi deteksi arus masuk

Recognises transformer inrush from the second harmonic and blocks false trips.

Id>ANSI 87

Perlindungan diferensial

Compares the currents into and out of the plant and clears faults inside the zone fast.

Fitur perangkat lunak

01Ia memiliki lingkungan perangkat lunak yang kuat dan mudah digunakan untuk mengatur berbagai fungsi
02Kemampuan untuk merekam hingga 200 osilografi, log perjalanan
03Memiliki 4 kelompok pengatur
04Modul perangkat lunak Perutean Sinyal untuk menetapkan sinyal fungsi ke input dan output relai
05Kemampuan untuk mengeluarkan pengaturan relai dalam format XRio

Sertifikat relai

  • Lembaga Penelitian Tenaga